WireWicket / Field calculation 02
Single- and three-phase voltage drop
Estimate voltage drop from phase, system voltage, load, one-way run length, conductor material, and conductor size. The example values are a starting fixture, not a recommendation.
Calculation inputs
Enter a finite voltage greater than 0 V.
Enter a finite load current of 0 A or greater.
Enter a finite one-way length of 0 ft or greater.
Single-phase mode estimates a two-conductor run using the selected material and conductor size.
Single-phase result
- Voltage drop
- 7.90 V
- Voltage drop percentage
- 6.58%
- Calculation inputs
- 120 V system · 20 A · 100 ft one way · Copper · 12 AWG (6,530 CM)
Voltage drop ÷ system voltage × 100
Calculation basis
Resistance-only estimate at 75°C using Vdrop = 2 × K × I × L ÷ CM. K = 12.9 for Copper; I is load current in amperes, L is one-way length in feet, and CM is conductor area in circular mils.
This estimate does not model conductor reactance, load power factor, or temperature changes.
Source: NCCER Electrical Formula Sheet